The low U-values that can be achieved by using the
Kingspan TEK Building System e.g. 0.22 W/m²·K in a wall and 0.18 W/m².K in a roof
with no additional insulation, mean that not only can the System meet
and
exceed current Building Regulations / Standards but it also
can meet the U-values that are expected to be set in future
changes to the Building Regulations / Standards in 2012 and
beyond. Extremely low U-values e.g. 0.10 W/m²·K, can also
easily be achieved with the Kingspan TEK Building
System by applying additional insulation e.g. Kingspan Kooltherm K18 Insulated Plasterboard. This means low running costs
and impressive comfort for the lifetime of the building.
In addition to the Kingspan TEK Building
System panel’s
excellent thermal performance, the closed cell structure of
its rigid urethane insulation core does not allow movement
of air within the wall. The insulation will not sag or physically
deteriorate over time as may be the case with other insulating
materials.
The proprietary jointing system used with the Kingspan TEK Building System can create a very air-tight structure (air permeabilities as low as 1 m³/hour/m² at 50 Pa) with little
opportunity for air leakage.
U-value calculations for a conventional timber framed house
always have to take into account the effects of cold bridging. Cold bridging
occurs where a material with a significantly worse thermal
conductivity interrupts the normal continuous layer of insulation.
The 15% figure includes:
- 38 mm timbers at 600 mm centres for 1 and 2 storey
buildings; and
- all timbers such as noggins (also known as repeated cold
bridges).
The 15% figure does not include:
- timbers that are outside the wall area used for heat loss
calculations;
- timbers (max. depth 50 mm) around window zones
and lintels (max. depth 175 mm); and
- intermediate floor joists
that are not insulated behind.
The SIP technology, upon which the Kingspan TEK Building
System is based, means the insulation layer is not interrupted
by repeating studwork. Therefore there is less cold bridging which can yield
a better thermal performance. There are however some cold
bridges e.g. where timbers are used to support point loads etc.
However, as with U-value calculations for timber frame the
same rules apply for timbers that do not have to be included. |